Smart Box Accessories
Smart Box level gauge accessories: Pressure and mechanical probes for accurate readings in unpressurized tanks, and interface modules supporting 4-20mA, 0-5V, or Modbus communication.
_edited.png)
Hydrostatic Pressure Sensor
Measurement range 250mbar
Hydrostatic Pressure Sensors for Non-Pressurized Tanks with a Liquid Operating Medium
Operating Media:
Waste oil, diesel, urea solution (AdBlue), fuel oil, biofuel, industrial oil, and rainwater.
Function:
-
Level probes are equipped with a pressure sensor to measure the hydrostatic pressure of a liquid column. The electronics in the level probe convert the signal into a 4-20 mA output signal.
Technical Data:
-
Extension of the probe cable up to a maximum of 200 m.
-
Measurement Range 250 mbar:
-
Urea solution (AdBlue): Up to 2.30 m tank height
-
Fuel oil: Up to 2.90 m tank height
-
Water: Up to 2.50 m tank height

Hydrostatic Pressure Sensor
Measurement range 500mbar
Hydrostatic Pressure Sensors for Non-Pressurized Tanks with a Liquid Operating Medium
Operating Media:
Waste oil, diesel, urea solution (AdBlue), fuel oil, biofuel, industrial oil, and rainwater.
Function:
-
Level probes are equipped with a pressure sensor to measure the hydrostatic pressure of a liquid column. The electronics in the level probe convert the signal into a 4-20 mA output signal.
Technical Data:
-
Extension of the probe cable up to a maximum of 200 m.
-
Measurement Range 500 mbar:
-
Urea solution (AdBlue): Up to 4.60 m tank height
-
Fuel oil: Up to 5.80 m tank height
-
Water: Up to 5.00m tank height

Hydrostatic Pressure Sensor
Measurement range 1000mbar
Hydrostatic Pressure Sensors for Non-Pressurized Tanks with a Liquid Operating Medium
Operating Media:
Waste oil, diesel, urea solution (AdBlue), fuel oil, biofuel, industrial oil, and rainwater.
Function:
-
Level probes are equipped with a pressure sensor to measure the hydrostatic pressure of a liquid column. The electronics in the level probe convert the signal into a 4-20 mA output signal.
Technical Data:
-
Extension of the probe cable up to a maximum of 200 m.
-
Measurement Range 1000 mbar:
-
Urea solution (AdBlue): Up to 9.20 m tank height
-
Fuel oil: Up to 11.6m tank height
-
Water: Up to 10m tank height

Hydrostatic Pressure Sensor- EX
Measurement range 250mbar
Hydrostatic Pressure Sensors for Non-Pressurized Tanks with a Liquid Operating Medium
Operating Media:
Kerosene and petrol
Function:
-
Level probes are equipped with a pressure sensor to measure the hydrostatic pressure of a liquid column. The electronics in the level probe convert the signal into a 4-20 mA output signal.
Technical Data:
-
Extension of the probe cable up to a maximum of 200 m.
-
high-strength FEP cable with Teflon double sheath
-
Measurement Range 250 mbar:
-
Petrol up to 3.30 m tank height
-
Tank connector: G 1 M

Mechanical level indicator type FSA-W
Measurement range 250mbar
For unpressurized tanks containing liquid operating media in dry and protected rooms (measuring accuracy: ± 2%),
Operating media: Waste oil, diesel fuel, FAME, urea solution (AdBlue®), heating oil, organic heating oil, vegetable oil, rainwater, and other water-polluting, non-flammable liquids.
Function: The tank content is determined by measuring the filling level using the float principle. The FSA-W 4-20 mA converts the measurement result into a current signal and passes it on to the SmartBox® digital display device using a cable. On the scale of the mechanical level indicator type FSA-W 4-20 mA, the tank contents can be read continuously in centimeters as the filling height.
Technical data:
-
Extension of the probe cable up to a maximum of 100 m
-
Measuring range: 0 to 2.40 m tank height
-
Tank connection: G 1 1/2
-
Protection class: IP30
-
Connection cable: 10 m
-
Diameter float type FSA-W 4-20 mA: 38 mm
_edited.png)
Data Transfer Module
Optional plug in to allow for communications between the Smart Box Gauge and the site BMS (business management system).
Available in:
-
4-20mA
-
0-5v
-
Modbus